Specifications

CG-PRC007-EN34
Performance
Data — 60 HZ
10–30 Ton
Part Load
Percent Entering Condenser Air Temperature (Degrees F)
Load 75 85 95 105 115 120
EER 12.9 11.3 9.8 8.4 7.2 6.6
100 Capacity 25.4 24.3 23.1 21.9 20.6 19.9
System KW 23.6 25.8 28.3 31.1 34.3 36.0
EER 14.1 12.4 10.8 9.3 8.0 7.4
60 Capacity 16.3 15.6 14.8 14.0 13.2 12.8
System KW 13.9 15.1 16.5 18.0 19.7 20.7
EER 12.9 11.1 9.4 8.0 6.7 6.1
40 Capacity 10.6 10.1 9.5 9.0 8.3 8.0
System KW 9.9 11.0 12.1 13.5 15.0 15.7
Notes:
1. Data based on 0.0001 fouling factor at sea level.
2. Interpolation between points is permissible.
3. Extrapolation beyond points is not permissible.
4. EER - Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power
5. Ratings based on evaporator drop of 10°F
6. Rated in accordance with ARI Standard 550/590-98.
7. Data obtained assuming 400 Volt supply.
Table PD-22 — 25 Ton — CGAF-C25
Table PD-20 — 15 Ton — CGA 180
Percent Entering Condenser Air Temperature (Degrees F)
Load 95 66.2
EER 13.8 -
100 Capacity 12.6 -
System KW 11.0 -
EER - 10.7
50 Capacity - 5.5
System KW - 6.3
Table PD-19 — 10 Ton — CGA 120
Percent Entering Condenser Air Temperature (Degrees F)
Load 95 66.2
EER 10.0 -
100 Capacity 8.7 -
System KW 10.5 -
EER - 10.1
52 Capacity - 3.5
System KW - 4.2
Table PD-23 — 30 Ton — CGAF-C30
Percent Entering Condenser Air Temperature (Degrees F)
Load 75 85 95 105 115 120
EER 13.0 11.3 9.8 8.4 7.2 6.7
100 Capacity 30.8 29.5 28.0 26.6 25.0 24.3
System KW 28.5 31.2 34.3 37.7 41.6 43.7
EER 13.4 11.9 10.4 9.1 7.8 7.3
50 Capacity 16.5 15.8 15.0 14.2 13.4 13.0
System KW 14.7 15.9 17.3 18.8 20.5 21.5
Table PD-21 — 20 Ton — CGAF-C20
Percent Entering Condenser Air Temperature (Degrees F)
Load 75 85 95 105 115 120
EER 13.1 11.4 9.8 8.3 7.1 6.5
100 Capacity 19.5 18.6 17.7 16.7 15.7 15.1
System KW 17.8 19.6 21.7 24.0 26.7 28.1
EER 14.4 12.7 11.1 9.6 8.2 7.5
50 Capacity 10.5 10.0 9.6 9.1 8.5 8.2
System KW 8.7 9.5 10.4 11.4 12.5 13.1