EER Performance Test Results
Customer G100823571-Mainstream Date 8/17/2012
Test Request ID G100596614-146 Time 13:21:09
Psy Room 5Ton Average time 0:30:00
Test Type 82° Baseline Test Number 83
Conditions 80/67-112 Engineer Ana Ruiz
ID Unit Model CAPF3642C6DB Tech Solomon Johnson
ID Unit Serial 1204564609 ID Coil Model CAPF3636A6
OD Unit Model SSX140361BB ID Coil Serial NA
OD Unit Serial 1203174536 Unit capacity 3
Refrigerant type R410A ID Unit type PSC Air Handler
Refrigerant charge factory charge 98 oz-23 oz Volt min/max/phs 208/230/1
Average Data without WattSaver Average with WattSaver % Delta
ID Inlet Dry Air 80.00 F 80.00 F 0.00%
ID Inlet Wet Air 67.00 F 67.00 F -0.01%
ID Outlet Dry Air 62.74 F 58.59 F -6.61%
ID Outlet Wet Air 60.21 F 57.36 F -4.73%
OD Inlet Dry Air 81.98 F 81.97 F -0.02%
Total Air Flow 1503.8 SCFM 1078.2 SCFM -28.30%
Unit Total Static 0.24 "H20 0.236 "H20 -1.67%
Total Power 2845 W 2491 W -12.44%
Net Sensible Capacity 28867 Btu/Hr 25761 Btu/Hr -10.76%
Net Latent Enthalpy 5214 Btu/Hr 7914 Btu/Hr 51.78%
Air Side Only Cap 34085 Btu/Hr 33682 Btu/Hr -1.18%
Air Side Only EER 11.98 EER 13.52 EER 12.89%
Compressor flow rate 491.29 lbs/hr 482.97 lbs/hr -1.69%
Compressor discharge temp 146.53 F 141.64 F -3.34%
OD Service Valve Liquid 304.5 PSIG 302.64 PSIG -0.61%
OD Service Valve Liquid temp 96.98 F 96.57 F -0.42%
Service Valve Sat Liquid 96.78 F 96.37 F -0.42%
Service Valve SC Liquid -0.19 ∆F -0.21 ∆F 10.53%
Evaporator Liq ID temp 95.9 F 95.48 F -0.44%
Evaporator ID Gas temp 66.03 F 58.8 F -10.95%
OD Service Valve Gas 145.83 PSIG 140.98 PSIG -3.33%
OD Service Valve Gas temp 65.93 F 58.77 F -10.86%
Service Valve Sat Gas 51.1 F 49.22 F -3.68%
Service Valve SC Gas 14.8 ∆F 9.53 ∆F -35.61%
Service Valve Suction temp 67.22 F 60.31 F -10.28%
Comments: Baseline test completed with fan on the high speed tap setting per the clients request.