EER Performance Test Results
Customer G100823571-Mainstream Date 8/17/2012
Test Request ID G100596614-146 Time 22:31:55
Psy Room 5Ton Average time 0:30:00
Test Type 82° Baseline Test Number 92
Conditions 80/67-112 Engineer Ana Ruiz
ID Unit Model ARUF374316CA Tech Solomon Johnson
ID Unit Serial 1204695348 ID Coil Model NA
OD Unit Model SSX140361BB ID Coil Serial NA
OD Unit Serial 1203174536 Unit capacity 3
Refrigerant type R410A ID Unit type PSC Air Handler
Refrigerant charge factory charge 6#2 oz-14 oz Volt min/max/phs 208/230/1
Average Data without WattSaver Average with WattSaver % Delta
ID Inlet Dry Air 80.00 F 80.00 F 0.00%
ID Inlet Wet Air 67.01 F 67.00 F -0.01%
ID Outlet Dry Air 64.51 F 60.93 F -5.55%
ID Outlet Wet Air 61.40 F 58.91 F -4.06%
OD Inlet Dry Air 81.98 F 81.99 F 0.02%
Total Air Flow 1897.1 SCFM 1307.6 SCFM -31.07%
Unit Total Static 0.236 "H20 0.208 "H20 -11.86%
Total Power 2868 W 2511 W -12.45%
Net Sensible Capacity 32647 Btu/Hr 27800 Btu/Hr -14.85%
Net Latent Enthalpy 3227 Btu/Hr 7030 Btu/Hr 117.85%
Air Side Only Cap 35877 Btu/Hr 34836 Btu/Hr -2.90%
Air Side Only EER 12.51 EER 13.87 EER 10.87%
Compressor flow rate 409.14 lbs/hr 393.08 lbs/hr -3.93%
Compressor discharge temp 143.45 F 138.57 F -3.40%
OD Service Valve Liquid 301.16 PSIG 298.95 PSIG -0.73%
OD Service Valve Liquid temp 96.07 F 95.53 F -0.56%
Service Valve Sat Liquid 96.03 F 95.52 F -0.53%
Service Valve SC Liquid -0.04 ∆F -0.01 ∆F -75.00%
Evaporator Liq ID temp 94.58 F 93.99 F -0.62%
Evaporator ID Gas temp 79.85 F 60.8 F -23.86%
OD Service Valve Gas 157.53 PSIG 151.84 PSIG -3.61%
OD Service Valve Gas temp 70.05 F 62.55 F -10.71%
Service Valve Sat Gas 55.45 F 53.36 F -3.77%
Service Valve SC Gas 14.6 ∆F 9.17 ∆F -37.19%
Service Valve Suction temp 70.82 F 63.49 F -10.35%
Comments: Baseline test completed with fan on the high speed tap setting per the clients request.