Install Instructions
Step 5.  Install the QwikPure TripleGuard™ Air Purier
If mounting on a duct board surface:
Insert the QwikPure TripleGuard™ into the duct, using the four remaining mounting 
studs to locate the QwikPure TripleGuard™ unit. Secure the Qwik Pure Triple Guard™ 
to the mounting ange studs with the four wing nuts supplied. 
If mounting on a metal surface:
a.  Hold the exterior mounting ange against the metal duct and cut an opening 
along the inside opening of the ange. Before cutting, make certain the QwikPure 
TripleGuard™ will t in the planned space. (see Figure 1). Cut an opening along 
the inside opening of the ange.
b.  Discard the mounting bracket. Using self-tapping sheet metal screws, secure the 
QwikPure TripleGuard™ directly to the sheet metal surface.
Step 6.  Connect to a Power Source
For optimal performance and maximum bulb life, the QwikPure TripleGuard™ should 
be operated continuously. However, using a relay (activated by the G and common 
wires), the QwikPure TripleGuard™ can also be operated only when the indoor blower 
is operating.
The QwikPure TripleGuard™ can be connected to any AC power source between 120 
and 240 VAC. We suggest that the power be drawn from the air handler or furnace 
power source downstream of the air handler or furnace breaker however any AC power 
source from 120 to 240 VAC can be used.
The electrical connection should be performed by a licensed electrician and conform to 
local electrical codes.
A rubber grommet is provided. Use the grommet to seal and protect the power cord 
as it passes through the sheet metal of the air handler. The securing strap is used to 
prevent any strain on the power cord. Drill a ½" diameter hole to accept the grommet 
into the sheet metal.
The power source must be fused. Two fuse cases with fuses are supplied. If connecting 
to 120 VAC, then only one fuse assembly on the hot (black)wire is needed. However, if 
connecting to 240 VAC both lines are hot, so a fuse is provided for each lead. Connect 
these fuses between the air handler power source and the QwikPure TripleGuard™ 
power lead, downstream of any air handler disconnect.
Ensure the green ground wire is properly grounded.
Step 7.  Verify proper operation
 f After successfully completing the previous steps, turn the unit on. 
 f The GREEN LED is illuminated indicating proper power to the unit. 
 f The two ORANGE LEDs are illuminated indicating both UV-C bulbs are operating 
properly.