QT2730 QwikPure TripleGuard™ EPA Est.
How it Works...
QwikPure TripleGuard™ Industrial-Grade Air Purifier/Sanitizer by Mainstream Engineering Corporation® With proper care, this advanced purification system will provides you with years of fresh, clean, odor-free air. For safety reasons and to maximize performance of this unit, please read the manual completely and ensure you understand that all safety and assembly instructions are understood before proceeding.
Replaceable Activated Carbon Potassium Permanganate Purifier AC/PP access plate Photocatalytic oxidation surfaces Two replaceable UV-C bulbs Electronics control module Green system ON-LED, Dual orange LEDs to indicate proper UV bulb function (one for each UV-C bulb) ON/OFF power switch Built to Last – Industrial-Grade Design ` Multiple voltage capability allows the system to operate on 120, 208 or 240 VAC single-phase.
Step 2. Install UV-C bulbs and purifier Install UV-C bulbs 1. Two replaceable UV-C bulbs are shipped with this unit. Carefully remove bulbs from their packaging. 2. Insert one bulb into each of the two bulb sockets located behind the front facing plate. Handle carefully, from the bulb base, and avoid touching the glass. 3. Slide the socket end of each bulb, through the oval opening in the back plate. Aalign and insert bulb socket pins with the socket pin holes at the front plate of the unit. 4.
Ideally, the QwikPure TripleGuard™ Air Purifier should be located in the center of the air flow of the duct, that is midway between the sides of the duct. The QwikPure TripleGuard™ must be installed into the ductwork in a location that cannot be viewed by anyone during routine operation of the system or during air filter changing. LOOKING DIRECTLY AT AN ILLUMINATED UNIT WILL CAUSE DAMAGE TO EYES.
Step 5. Install the QwikPure TripleGuard™ Air Purifier If mounting on a duct board surface: Insert the QwikPure TripleGuard™ into the duct, using the four remaining mounting studs to locate the QwikPure TripleGuard™ unit. Secure the Qwik Pure Triple Guard™ to the mounting flange studs with the four wing nuts supplied. If mounting on a metal surface: a. Hold the exterior mounting flange against the metal duct and cut an opening along the inside opening of the flange.
Step 8. Educate the Homeowner Complete and attach the Next Service Date sticker on the access cover with a date approximately 12 months from the install date for both the UV-C bulbs and the AC/PP purifier. Warn the homeowner to never take the unit out of the duct work without first turning the power switch off. Explain that all service must be performed by a licensed HVAC professional or the warranty will be voided. Explain the danger of looking at the light emitted from the QwikPure TripleGuard™ unit.
Step 4. Replace the AC/PP purifier and complete the installation. a. Insert a new AC/PP unit into the QwikPure TripleGuard™ by sliding the unit into the guides. b. Replace the AC/PP access cover. c. Install a new Next Service sticker with the replacement date for the AC/PP purifier appropriately 12 months from today’s date. Transfer the bulb replacement date to the sticker as well. d. Turn power back on and check for proper function. All three LEDs will be illuminated.
Step 5. Remove the UV-C Bulbs Carefully remove the two UV-C bulbs from the QwikPure TripleGuard™ unit by sliding them out the end of the unit, through the clearance holes. Dispose of these bulbs in the same manner as any other fluorescent bulb. These bulbs contain mercury and must be disposed of properly. Step 6. Clean the PCO surfaces Use a clean damp cloth to clean dust and debris from all surfaces of the QwikPure TripleGuard™ unit, including the photocatalytic oxidation surfaces. Step 7.
Warn the homeowner to never take the unit out of the duct work, without first turning the power switch off. Explain that all service must be performed by a licensed HVAC professional or the warranty will be voided. Explain the danger of looking at the light emitted from the QwikPure TripleGuard™ unit Show the homeowner the Green LED and Orange LEDs, and explain that they should be checked ideally with every air filter change or at least a few times a year.
QT2730 QwikPure TripleGuard™ Industrial-Grade Air Purifier/Sanitizer by Mainstream Engineering Corporation 200 Yellow Place Rockledge, Florida 32955 CONTACT info@mainstream-engr.com www.qwik.com CALL FOR SUPPORT 1-800-866-3550 or 1-321-631-3550 QwikProducts™, QwikPure TripleGuard™ are trademarks and Mainstream Engineering Corporation® is a registered trademark of Mainstream Engineering Corporation.