14.2 COMMAND AND CONTROL PANEL
BEFORE CARRYING OUT THE OPERATION TEST, READ CAREFULLY AND ACQUIRE A GOOD KNOWLEDGE OF THE
COMMAND FUNCTIONS.
FIG.
14
2
1) Control
card
2) Emergency stop button
with mechanical lock and
rotation release
1
14.3 CONTROLLER (Standard controller for fixed speed compressors )
10
12
8
FIG. 15
9
3
13
15
11
2
7
S3
1
4
5
16
14
17
6
There is an electronic controller on the electric panel ; this controller includes the display of the functions as shown in figure 15.
1 Stop button (0) 10 Automatic operation led
2 Start button (I) 11 Automatic operation symbol
3 Display 12 Service warning led
4 Reset button 13 Service warning symbol
5 Enter key 14 Downward scroll key
6 Voltage on led 15 Upward scroll key
7 Voltage on symbol 16 Left scroll key
8 General alarm led 17 Right scroll key
9 General alarm symbol
CAUTION: WAIT AT LEAST 20 SECONDS BEFORE STARTING THE MACHINE AFTER SWITCH OFF.
Introduction:
The controller performs the following functions:
- Compressor control
- Compressor protection
- Maintenance monitoring
- Automatic restart after supply interruption (optional).
Automatic control of the compressor
The controller maintains the outlet pressure within defined limits, commanding the load and unload operations of the compressor. Various
parameters are considered, among them are: the unload pressure, the load pressure, the minimum stop time and the maximum number of motor
starts.
Compressor protection
Shutdown
If outlet temperature of the element exceeds the programmed shut down level, the compressor will be stopped. This will be indicated on the display
(3). The compressor will also stop if a motor overload occurs.