Product specifications
7
Zone control of DPW unit
Zone control of the DPW unit is performed by a zero voltage or X-X contact from
a relay or zone control panel closing when unit operation is required.
The DPW unit should have two Brown low voltage wires connected into the
microprocessor to facilitate this. It is possible depending on the production date
of the unit, that these wires are supplied loose for field installation. If this is the
case the following procedure should be followed to allow the units to be zoned.
1. Take wires provided and located the center electrical plug connection to
the microprocessor.
2. Insert wires into the empty slots located second from the bottom (above
connections with Yellow wires – see photo). Insert wire (electrical
connector end) into the empty slots, a click should be heard and the wire
should not pull loose.
3. With the two wires inserted into the microprocessor, power the unit on
using the DSR-100 controlller.
Insert Wires
here