Product specifications
DSR-100F
NOTES
TO SET DSR-100F
1 PRESS UNIT ON/OFF BUTTON
2 PRESS HEATING SET TEMP
BUTTON (LHS OF ON/OFF BUTTON)
YEL
3 USE UP AND DOWN ARROWS
TO SELECT DESIRED HEATING
YEL
WATER TEMPERATURE
RANGE 122-176 DEGF
BRN BRN
4 PRESS DHW SET TEMP
BUTTON (RHS OF ON/OFF BUTTON)
5 USE UP AND DOWN ARROWS
TO SELECT DESIRED DHW
WATER TEMPERATURE
98-114 DEGF, 120, 130, 140 DEGF
WHEN DRY CONTACT IS CLOSED UNIT
WILL START AND PROVIDE CLOSED
LOOP HEATING WATER AT THE
TEMPERATURE SELECTED
DHW PRIORITY WILL BE MAINTAINED
WHEN THE ZONE(S) SATISFY THE UNIT
WILL SHUT DOWN, DSR WILL REMAIN LIT
AT ALL TIMES
THIS IS THE PREFERRED METHOD TO
INTEGRATE ZONE VALVES AND
THE SECONDARY LOOP PUMP
8750 Pioneer Blvd, Santa Fe Springs CA 90670
Tel : 562 699 6066, Fax : 562 699 4351, Web : www.Quietside.com
Title : DPW & TACO ZVC ZONE CONTROL PANEL WIRING
Drg # : QUI-ZCW-005 Drawn : JLM 10/17/2008 Rev : 001
DPW
DPWH
To Secondary
Pump Control
e.g. Taco
SR501