Technical Specifications
Reading Indication Action
Between high & Good System is connected properly. No
low resistance limits action is necessary.
Higher than Open Circuit Check all electrical connectors
high resistance limit and recrimp or replace any that
are attached improperly.
Zero (0) Short Circuit Check the path that the wiring is
taking and make sure that no
wires are attached to both bus
bars of a single panel. If any are,
remove the wires
After any remedies have been performed for open or short circuits, if
any, retest the system.
COMPLETE THE INSTALLATION
1. Install control device and connect to electrical panel box.
Install and wire the control device according to manufacturer’s
instructions in the junction box added at the beginning of
Part 3 — Installation.
2. Install thermal insulation.
The insulation may be installed in the normal manner.
3. Finish the floor in any normal fashion.
4. Install a floor covering in accordance with the designer’s notes.
13
NOTE
Tuck insulation up at the end of each panel set so that it seals in the
heating panel set. This will help keep heat from escaping and improve
the efficiency of the system.
See page 3 for more
information about
thermal insulation.
Any material used as
a floor surface must
be appropriate as
noted on page 2.
Follow the guidelines
on page 2 for floor
finishes.
Tuck Insulation Up
CM1004 FLOOR - 2003-09-16.qxd 9/17/2003 2:59 PM Page 15