Technical Specifications
3. Insulate the other end of each bus bar.
Place a length of electrical tape over the exposed end of each
bus bar opposite the electrical connector.
INSTALLATION
Do not pierce the
panels within 3/8
inch / 10 mm of the
bus bar or heating
portion of the panel.
The heating panels
must run smooth and
flat between the
joists. There must be
no wrinkles in the
heating panels.
Heating panels must
run parallel to the
joists they are
attached to.
8
ATTACH HEATING PANEL SETS
1. Align a heating panel set with one of the joists to which it will be
attached. Make reference to the layout made in Part 1 for heating
panel locations.
2. Nail or staple the panel set in place, leaving at least 6 inches /
150 mm clearance to walls or partitions at the connector end for
wiring and final assembly. Nail or staple as close to the perforated
bending line as possible, keeping the edge of the panel set
straight along the top edge of the joist. Nails or staples must be
placed at least once every 12 inches / 300 mm along each side of
the heating panel set.
Electrical Tape
Nail or staple near
perforated fold line
CM1004 FLOOR - 2003-09-16.qxd 9/17/2003 2:59 PM Page 10