Technical data

86 • BACnet/IP Controller 750-830
Fieldbus Node Start-up
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
Note
To address additional fieldbus nodes, enter a similar text line for each node,
with your own specific data.
8. In the menu File select the menu item Save to store the changed settings in
the "bootptab.txt" file.
9. Close the editor.
3.1.7.2.4.2 BootP Server
1. On your PC, go to Start and select the menu item Programs \ WAGO
Software \ WAGO BootP Server.
2. Click on WAGO BootP server to open the dialog window.
3. Click on Start in the dialog window that then appears. This activates the
query/response mechanism of the BootP protocol.
A number of messages are then output at the BootP server. Error messages in-
dicate that some services (such as Port 67, Port 68) are not defined in the op-
erating system.
Fig. 3-13: Dialog window for the WAGO-BootP Server, with messages P012909d
4. To close the BootP server again, click Stop and then click the button Exit.