Technical data

292 • List of all BACnet Properties in Native Operation
Local_Date
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
6.37 Local_Date
Data Type Date
Objects Device
Description The Local_Date property, of type Date, shall indicate the
date to the best of the device's knowledge. If the BACnet
Device does not have any knowledge of time or date, then
the Local_Date property shall be omitted.
6.38 Local_Time
Data Type Time
Objects Device
Description The Local_Time property, of type Time, shall indicate the
time of day to the best of the device's knowledge. If the
BACnet Device does not have any knowledge of time or
date, then the Local_Time property shall be omitted.
6.39 Location
Data Type CharacterString
Objects Device
Description This property, of type CharacterString, indicates the physi-
cal location of the BACnet Device.
6.40 Low_Limit
Data Type REAL
Objects Analog input, Analog output
Description This property, of type REAL, shall specify a limit that the
Present_Value must fall below before an event is generated.
This property is required if intrinsic reporting is supported
by this object.