Technical data
152 • BACnet/IP Controller 750-830
BACnet Building Controller (B-BC)
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
3.1.12.2.2 Analog Output Object
The Analog Output object defines a standardized object whose properties rep-
resent the externally visible characteristics of an analog output.
The Analog Output Object and its properties are summarized in Tab. 3-29.
The properties are described in section 6.
Tab. 3-29: Properties of the Analog Output Object
Property Data type: Default Value Writable via BACnet by
means of
Object_Identifier BACnetObjectIdentifier - -
Object_Name CharacterString Analog_Output_X -
Object_Type BACnetObjectType ANALOG_OUTPUT -
Present_Value REAL - -
Description CharacterString *see footnote WriteProperty
Device_Type CharacterString ' ' WriteProperty
Status_Flags BACnetStatusFlags '000' -
Event_State BACnetEventState State_Normal (0) -
Reliability BACnetReliability 0 WriteProperty
Out_Of_Service BOOLEAN '0' -
Units BACnetEngineeringUnits NO_UNITS (95) WriteProperty
Min_Pres_Value REAL 0 -
Max_Pres_Value REAL 0 -
Resolution REAL 0 -
Priority_Array BACnetPriorityArray - -
Relinquish_Default REAL 0 WriteProperty
COV_Increment REAL 0 WriteProperty
Time_Delay Unsigned 0 WriteProperty
Notification_Class Unsigned 0 WriteProperty
High_Limit REAL 0 WriteProperty
Low_Limit REAL 0 WriteProperty
Deadband REAL 0 WriteProperty
Limit_Enable BACnetLimitEnable '111' WriteProperty
Event_Enable BACnetEventTransitionBits '111' WriteProperty
Acked_Transitions BACnetEventTransitionBits '111' -
Notify_Type BACnetNotifyType Alarm (0) WriteProperty
Event_Time_Stamps BACnetARRAY[3] for BACnet-
TimeStamp
UNSPECIFIED -
*corresponds to the item number of the module