Technical data

140 • BACnet/IP Controller 750-830
BACnet Building Controller (B-BC)
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
Ability to synchronize its internal clock upon request
Ability to perform re-initialization upon request
Ability to upload its configuration and allow it to be subsequently restored
Commands for half routers for establishing and breaking off connections
Tab. 3-27: BIBBs of the B-BC shows the minimum requirement for the BIBBs
for the B-BC in general as well as additional BIBBs implemented by the
WAGO BACnet/IP Controller.
Tab. 3-27: BIBBs of the B-BC
IOB
BIBBs of the B-BC
(Minimum requirements)
Additional BIBBs of the
WAGO BACnet/IP Controller
Data Sharing
DS-RP-A,B
DS-RPM-A,B
DS-WP-A,B
DS-WPM-B
DS-COVU-A,B
DS-COV-A,B
DS-COVP-A,B
Alarm and Event Management
AE-N-I-B
AE-ACK-B
AE-INFO-B
AE-ESUM-B
Scheduling
SCHED-E-B
SCHED-A
SCHED-I-B
Trending
T-VMT-I-B
T-ATR-B
Device Management
DM-DDB-A,B
DM-DOB-A,B
DM-DCC-B
DM-TS-B
or
DM-UTC-B
DM-RD-B
DM-BR-B
NM-CE-A