Programming the PFC Using WAGO-I/O-PRO CAA
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
3.1.8.6.2 Transfer via Fieldbus
The physical link between the PC and the controller is set up via fieldbus.
An appropriate communication driver is required for data transfer. The driver
and its parameters must be entered in the WAGO-I/O-PRO CAA in the dialog
window "Communication parameters".
1. Start the WAGO-I/O-PRO CAA software under Start / Programs / WAGO-
I/O-PRO and WAGO-I/O-PRO CAA, or by clicking the program icon on
the desktop.
2. In the menu Online select the item Communication parameters.
The dialog window "Communication parameters" then appears. This window
is empty in its default settings.
3. Click New to set up a connection and then specify a name.
4. In the selection window mark the desired driver on the right-hand dialog
side (e.g. TCP/IP), to configure the serial connection between PC and the
controller).
The following standard entries are shown in the center dialog window:
Address: the IP address of the controller
Port: 2455
Motorola byteorder: No
Change any entries as you may require.
You have now configured the TCP/IP link with the communication parame-
ters/drivers.
Note
The controller must have an IP address before it can be accessed. The con-
troller mode selector switch must be set to the center or top position.
5. Under Online, click the menu item Login to log in to the controller.
(The WAGO-I/O-PRO CAA Server is active during online operation. The
communication parameters cannot be called up during this time.)
If there is no program in the controller, a window now appears asking whether
or not the program is to be loaded.
6. Respond with Yes to load the current program.
7. Once the program has been loaded, start program processing in the menu
Online, menu item Start.
"ONLINE" and "RUNNING" will then appear at the right of the status bar.
8. To terminate online operation, click the menu item Log off in the Online
menu.