Specifications
BACnetT‐StatUser’sManualRev1.1,7/28/11 Page|4
4. MountthePlate‐Dressthewiresthroughthecenterwindowonthebackplateandinstall
mountingscrews.Tightenscrewstoensuretheplateismountedsecurely,butdonotover
tightenandwarpthebackplate.
2.2Wiring
1. TerminatetheWireConnections–Cutoffexcesswire,dresswireflushtothebackpaneland
strip1/4”ofinsulationtoexposeconductor.InsertandtightenusingtheWireTerminations
diagram.
2. ConnectionDescriptions:
ZONE+
Formountingaremotetemperaturesensor,setJumper
ZONE–
J1/2totop&middleandSENSSPOTtooffonfrontpanel
SUPPLY+
SupplyDucttemperaturesensor
SUPPLY–
FANP+
FANProofofRuncurrenttransducer
FANP–
MA+
24mAinputforoptionalsensor
MA24/‐
“Onfuturemodels”
DIN+
Digitalinputforoptionalinput
DIN–
“Onfuturemodels”
AOP+
Analogoutputforadditionalcontrol
AOP–
“Onfuturemodels”
BUSD0‐
BusWirefromQuestBACnetRouterandthenonto
BUSD1+
additionalT‐Stats
BUSC
R
24VACpower‐red
C
24VACcommon‐black
FANG
FanControl–green
COOLY1
CallforCool,stage1‐yellow
COOLY2
CallforCool,stage2–Blue/Orange
HEAT
W1/B
CallforHeat,stage1‐white
HEATW2
CallforHeat,stage2–Varies
0
HeatPumpReversingValve‐orange
Figure2‐ConnectionDescriptions