Specifications

BACnetTStatUser’sManualRev1.1,7/28/11 Page|11
Instance Description Writable? Limits Default Notes
MI-2 Control Mode Y 1..4 1 1 – Auto (both cool and heat)
2 – Cooling only
3 – Heating only
4 - Off
MI-3 Operation Mode Status N 1..6 0 1 – Off
2 – Cooling stage 1
3 – Cooling stage 2
4 – Heating stage 1
5 – Heating stage 2
6 – Heating stage 3
Device Object Detail
Supported Properties Writable? Default Property Range
Restrictions
Notes
Object Identifier N 1 N/A Note that the device
object id is the
MSTP Network *
1000 + the MAC
address.
Object Name N QSTAT10000-0-1 N/A Built up with model
name-MSTP
Network Address-
MAC Address
Object Type N N/A N/A
Description N Qstat10000 N/A
Model Name N Qstat10000 N/A
System Status N N/A N/A
Vendor Name N Quest Controls N/A
Vendor Identifier N 506 N/A
Firmware Revision N Major.Minor.Bug N/A
Application Software
Version
N Major.Minor.Bug N/A
Protocol Version N 1 N/A
Protocol Revision N 5 N/A
Protocol Service Supported N See BIBB list above N/A
Protocol Object Types
Supported
N See Object list above N/A
Object List N Object Count N/A
Maximum APDU Length
Accepted
N 50 N/A
Segmentation Supported N Not supported N/A