Specifications

BACnetTStatUser’sManualRev1.1,7/28/11 Page|10
Instance Description Writable? Notes
255 – Remove bypass
BO-1 Output Y1 Y 0 – De-energize Output
1 – Energize Output
255 – Remove bypass
BO-2 Output Y2 Y 0 – De-energize Output
1 – Energize Output
255 – Remove bypass
BO-3 Output W1/B Y 0 – De-energize Output
1 – Energize Output
255 – Remove bypass
BO-4 Output W2 Y 0 – De-energize Output
1 – Energize Output
255 – Remove bypass
BO-5 Output O Y 0 – De-energize Output
1 – Energize Output
255 – Remove bypass
Multistate Input Object Detail
Supported Properties Writable? Property Range Restrictions
Object Identifier N N/A
Object Name N N/A
Description N N/A
Object Type N N/A
Present Value Y (some) Y
Status Flags N N/A
Event State N N/A
Out of Service N N/A
Number of States N N/A
Instance Description Writable? Limits Default Notes
MI-0 Baud Rate Y 1..5 3 1 – 9600 Baud
2 – 19200 Baud
3 – 38400 Baud
4 – 57600 Baud
5 – 76800 Baud
MI-1 HVAC Type Y 1..6 1 1 – Single Stage Conventional
2 – Dual Stage Conventional
3 – Heat Pump 1
4 – Heat Pump 2
5 – Gas Heat 1
6 – Gas Heat 2