Specifications

BACnetTStatUser’sManualRev1.1,7/28/11 Page|9
Supported Properties Writable? Property Range Restrictions
Present Value Y (Priority array not available) N/A
Status Flags N N/A
Event State N N/A
Out of Service N N/A
Polarity N N/A
Instance Description Writable? Default Notes
BV-0 Temperature Units Y 0 0 – Use Fahrenheit
1 – Use Celsius
BV-1 Occupied Fan Mode Y 0 0 – Fan mode auto
1 – Fan mode always on
BV-2 Unoccupied Fan Mode Y 0 0 – Fan mode auto
1 – Fan mode always on
BV-3 Force Occupied Mode Y N/A 0 – Remove BACnet occupied
override
1 – Enable BACnet occupied
override
BV-4 Zone Sensor Location Y 0 0 – Use onboard zone thermistor
1 – Use remote mounted zone
thermistor
Binary Output Object Detail
Supported Properties Writable? Property Range Restrictions
Object Identifier N N/A
Object Name N N/A
Description N N/A
Object Type N N/A
Present Value Y* N/A
Status Flags N N/A
Event State N N/A
Out of Service N N/A
Polarity N N/A
Priority Array Y* N/A
* - The binary output object utilizes the priority array 1 through 16. A BACnet client can see the system's output
desire at priority 16 and is free to write any of the other 15 priorities.
Instance Description Writable? Notes
BO-0 Output G Y 0 – De-energize Output
1 – Energize Output