Specifications

BACnetTStatUser’sManualRev1.1,7/28/11 Page|8
Instance Description Writable? Units Limits Default Notes
window.
Set both the Start and End values to
0 to mark this window as unused.
AV-51 Sun Sched Win 2 Start Y Minutes 0..1440 0 Number of minutes since midnight
to begin occupied mode for this
window.
AV-52 Sun Sched Win 2 End Y Minutes 0..1440 0 Number of minutes since midnight
to end occupied mode for this
window.
Set both the Start and End values to
0 to mark this window as unused.
AV-53 Curr User Spt Adjust Y TempF or
TempC
0..AV16 N/A The current setpoint offset a user has
entered via the front panel.
AV-54 Front Panel Code Y None 0,11..99 0 The access code a user must enter to
use the front panel programming
menu.
Binary Input Object Detail
Supported Properties Writable? Property Range Restrictions
Object Identifier N N/A
Object Name N N/A
Description N N/A
Object Type N N/A
Present Value N N/A
Status Flags N N/A
Event State N N/A
Out of Service N N/A
Polarity N N/A
Instance Description Writable? Notes
BI-0 Fan Proof N The current reading of the fan proof input.
Binary Value Object Detail
Supported Properties Writable? Property Range Restrictions
Object Identifier N N/A
Object Name N N/A
Description N N/A
Object Type N N/A