Specifications
BACnetT‐StatUser’sManualRev1.1,7/28/11 Page|3
Analog Input Object Detail
Supported Properties Writable? Property Range Restrictions
Object Identifier N N/A
Object Name N N/A
Description N N/A
Object Type N N/A
Present Value N N/A
Status Flags N N/A
Event State N N/A
Out of Service N N/A
Units N N/A
Instance Description Writable? Notes
AI-0 Raw Zone Temp N Fahrenheit or Celsius reading of the zone thermistor, directly from
the sensor (no offsets applied).
A reading of -25F indicates an open sensor condition and a reading
of 150F indicates a shorted sensor condition.
AI-1 Raw Supply Air N Fahrenheit or Celsius reading of the supply air thermistor, directly
from the sensor (no offsets applied).
A reading of -25F indicates an open sensor condition and a reading
of 150F indicates a shorted sensor condition.
Analog Value Object Detail
Supported Properties Writable? Property Range Restrictions
Object Identifier N N/A
Object Name N N/A
Description N N/A
Object Type N N/A
Present Value Y (some) Y
Status Flags N N/A
Event State N N/A
Out of Service N N/A
Units N N/A
Instance Description Writable? Units Limits Default Notes
AV-0 MAC Address Y None 1..127 1 MS/TP MAC address needs to be
unique in each network. You should
restart the unit after changing the