Specifications
GV200 @Track Air Interface Protocol
TRACGV200AN003 – 68 –
Analog Input ID3 1 3 3
Mode 1 0|1|2|3 0
Min Threshold <=4 250– 2700mV
Max Threshold <=4 250– 2700mV
Sample Rate <=2 0|1– 12(×2s) 0
Reserved 0,TBD
Output ID 1 0– 4
Output Active 1 0|1
Duration <=3 0– 255(×100ms) 0
Toggle Times <=3 0– 255 0
Sync with FRI 1 0|1 0
Reserved 0,TBD
Reserved 0
Reserved 0
Serial Number 4
0000~FFFF
Tail Character 1 $ $
<
Analog Input ID 1~3>: The analog input port ID.
<Mode>: Working mode of the analog input alarm (+RESP :GTMAI).
0: Disable analog input alarm.
1: Enable analog input alarm. If the current input voltage is within the range of (<Min
Threshold>, <Max Threshold>), the alarm will be triggered.
2: Enable analog input alarm. If the current input voltage is outside the range of
(<Min Threshold>, <Max Threshold>), the alarm will be triggered.
3: No alarm mode, only check the voltage, but no alarm will trigger.
<Min Threshold>: The lower limit to the voltage of the analog input port to trigger the alarm.
<Max Threshold>: The upper limit to the voltage of the analog input port to trigger the alarm.
<Sample Rate>: The sampling period of the analog input port.
<Output ID>: Specify the ID of the output port (1 to 4) to output specified wave shape when
the analog input alarm is triggered. If set to 0, no output wave.
<Output Active>: set the final status of the output port.
0: Disable status.
1: Enable status.
<Toggle Times>: The times of the square-wave.
<Sync with FRI>: The device can send the analog input voltage periodically along with fixed
report message. Set this field to 1 to enable it, 0 to disable.
Queclink
Confidential










