Quick Start Guide

2 Choosing a Location
SuperLoader 3 Quick Start Guide
Choosing a Location
The autoloader is designed to fit in a standard 19-inch rack using either the long or
short brackets (depending on the depth of the rack). The autoloader uses standard rack
mounting hardware.
Note: It is recommended that you review this entire document prior to beginning the
installation
Choose a location that meets the following criteria:
Preparing for the Installation
Before you begin the installation procedure in this section, make the following
preparations as described in this section:
Providing Necessary Tools
Taking ESD Precautions
Criteria Description
Rack requirements Standard 19-inch rack
Room temperature 10–35° C (50–95° F)
Power source AC power voltage: 100–127 VAC; 200–240 VAC
Line frequency: 50–60 Hz
Note: Locate the AC outlet near the autoloader. The AC
power cable is the product’s main disconnect device and
must be easily accessible at all times.
Weight 14.1 kg (31 lb.) unloaded
17.2 kg (38 lb.) loaded with 2 magazines, 16 cartridges
Air Quality Minimize sources of particulate contamination. Avoid areas
near frequently used doors and walkways, cooling or
exhaust vents, stacks of supplies that collect dust, printers,
and smoke-filled rooms.
Caution: Excessive dust and debris can damage tapes and
tape drives.
Humidity 20–80% RH (non-condensing)
Clearance Back: Minimum of 43.2 cm (17 in.)
Front: Minimum of 68.6 cm (27 in.)
Sides: Minimum of 5.08 cm (2 in.)