User's Manual

Chapter 8: Installing, Removing, and Replacing Components
Removing and Replacing the System Control Board
230 Quantum Scalar i40 and Scalar i80 User’s Guide
5 Access the Web client using the IP address and log in using the
default user name and password:
User name: ad
min
Password: passwor
d
6 Option
ally, install tape drive firmware for autoleveling. The library
firmware contains baseline tape drive firmware for autoleveling.
Verify your tape drive firmware is at the level you expect. If not:
a Upload the tape dr
ive firmware you want to use. From the Web
client, select Tools > Drive Operations > Upload/remove tape
drive firmware for autoleveling.
b Unl
oad all tape cartridges from the tape drives on which you
want to autolevel firmware.
c In
itiate autoleveling by doing one of the following:
Restart the library (from the operator panel, select Actions
>
Shutdown > Restart Library.
Restart all the tape drives you want
to autolevel, as follows:
From the Web client, select Tools > Diagnostics. Confirm
you want to take the partitions offline. Select Drives >
Drive Tests > Drive Reset. Select the applicable partitions
and tape drives, then click Apply, then click OK.
7 If
you changed the IP address from what it was originally, update
host and other applications that access the library.
8 Update the
library name, time zone, and any other configuration
settings, if required, using the Web client Setup menus.
9 Save
the library configuration. From the Web client, select Tool s >
Save/Restore Configuration. Select Save Configuration and click
Apply. Save the configuration to a known location.
10 It
is recommended that you run the Installation and Verification Test
(IVT). From the operator panel, select Too ls > I V T and follow the
instructions. The IVT takes about 30 minutes. If any problems are
detected, the library issues a diagnostic ticket.
11 P
ackage the old SCB in the packaging that shipped with the new
SCB and send the old SCB back to Quantum.