User's Manual
Chapter 8: Installing, Removing, and Replacing Components
Removing and Installing a Power Supply
220 Quantum Scalar i40 and Scalar i80 User’s Guide
10 Run the magazine diagnostics test on the replaced magazine to be
sure it is functioning correctly.
a Place a
scratch tape in the top I/E station slot.
b If
manual cartridge assignment is enabled, assign the scratch
tape to the System partition.
c F
rom the operator panel, select Tools > Diagnostics.
d Co
ntinue through the next few screens to run the magazine test
on the replaced magazine.
If a problem is found during testing,
you receive a diagnostic ticket.
See
Running the IVT Diagnostic Subtests Individually – Robotics,
Tape Drive, and Magazine Tests on page 257 more information.
Removing and Installing a Power Supply
The Scalar
®
i40 contains one power supply. The Scalar i80 can have up
to two power supplies for redundancy purposes.
An unused power supply slot must be covered by a filler plate.
This document covers:
•
Replacing a Power Supply in a Single-Power-Supply System (Scalar
i40 and Scalar i80)
• Adding or Replacing a Redundant Power Supply on the Scalar i80