4-6 System Specifications
6-01337-04 Rev A
Physical Specifications
For physical specifications for each library module, see Table
4-5.
If the Scalar 10K is installed on a raised floor, the raised floor
should be stabilized to prevent a horizontal shift of the raised
floor structure. The minimum overall floor load rating should
be 201 lb/ft
2
. Quantum recommends a floor load rating of
250 lb/ft
2
. These ratings do not include additional loading by
people and equipment traffic. The floor must support point
loads exerted by the leveling pads of up to 94 lb/in
2
.
The Scalar 10K has four point loads on the DM, CM, and TM
and six point loads on the AM and EM.
Table 4-5 Physical Specifications
Height Width Depth
Maximum
Weight
Distributed
Load
Point Load
a
a. The point load value is based on modules that have a foot size of 2.5 inches.
Control Module
76.69 in.
1,947.9 mm
29.59 in.
751.7 mm
22.44 in.
570 mm
700 lb
318 Kg
151.81 lb/ft
2
741.2 Kg/m
2
35.64 lb/in
2
2.51 Kg/cm
2
Accessor Module
76.69 in.
1,947.9 mm
65.65 in.
1,667.6 mm
29.53 in.
750.0 mm
1345 lb
610 Kg
99.90 lb/ft
2
487.8 Kg/m
2
45.67 lb/in
2
3.21 Kg/cm
2
Expansion Module
76.69 in.
1,947.9 mm
65.65 in.
1,667.6 mm
29.53 in.
750.0 mm
1360 lb
616 Kg
101.02 lb/ft
2.
493.2 Kg/m
2
46.18 lb/in
2
3.24 Kg/cm
2.
Drive Module - UDS
76.69 in.
1,947.9 mm
29.59 in.
751.7 mm
22.44 in.
570 mm
888 lb
403 Kg
192.58 lb/ft
2
940.2 Kg/m
2
45.24 lb/in
2
3.19 Kg/cm
2
Outside Tower Module
76.69 in.
1,947.9 mm
29.59 in.
751.7 mm
22.44 in.
570 mm
930 lb
422 Kg
201.69 lb/ft
2
984.61 Kg/m
2
47.38 lb/in
2
3.33 Kg/cm
2
Inside Tower Module
76.69 in.
1,947.9 mm
29.59 in.
751.7 mm
22.44 in.
570 mm
930 lb
422 Kg
201.69 lb/ft
2
984.61 Kg/m
2
47.38 lb/in
2
3.33 Kg/cm
2