User's Guide

4-4 System Specifications
6-01337-04 Rev A
Electrical Specifications
Both the Control Module (CM) and the Drive Module (DM)
require two AC power sources.
You must install your library with two different power
sources to have redundant power. You will NOT have
redundant power if you use only one AC power source. If a
power failure occurs, your library will fail.
The power cable length for each of these inputs is 14 feet
(4.26 m). Other electrical specifications for these modules are
shown in
Table 4-2.
The typical power consumption for each module is shown in
Table 4-3 on page 4-5.
Table 4-2 Electrical Specifications
Module
Voltage
a
(Single Phase)
a. Connect an 18 gauge stranded copper wire from the CM to earth ground.
Max
AMP
b
Rating
b. Includes the drive components.
United States
Power Connector
International Power
Connector
CM 208 - 240 20 L6 - 20 Plug is customer supplied
DM 208 - 240 16 L6 - 20
Caution