Operating instructions
6-20 Error Messages
6-00058-05 Rev A
35 00 00 A fatal SCSI error is detected but the port is unknown.
Action 1
Verify that the SCSI busses connected to both Library Ports (if applicable) are
properly terminated and powered.
Action 2
Verify that the SCSI ID is unique for the SCSI cable.
Action 3
Verify that both Library SCSI Ports are properly configured (if applicable) by
using the operator panel (Main Menu Setup Library SCSI Ports).
Action 4
If the problem is not corrected or persists, contact GCH. For GCH contact
information, refer to Getting More Information or Help on page 1-8.
39 00 00 An external network error was detected by the Remote Management Unit
(RMU).
Action 1
Ensure the network cable is properly connected to the RMU.
Action 2
Verify that the network the RMU is connected to is working properly.
Action 3
If the problem is not corrected or persists, contact GCH. For GCH contact
information, refer to Getting More Information or Help on page 1-8.
40 00 00 The Library Aisle power cannot be enabled.
Action 1
Verify th at the ai sl e doors are closed.
Action 2
Check the door fuses or reset the circuit breaker, as applicable.
Action 3
If the problem is not corrected or persists, contact GCH. For GCH contact
information, refer to Getting More Information or Help on page 1-8.
41 00 00 The Library Aisle power cannot be disabled, failures are detected in the
Digital In/Digital Out (DI/DO) circuitries.
Action 1
Contact GCH. For GCH contact information, refer to Getting More Information
or Help on page 1-8.