User's Guide
30  Troubleshooting and Diagnostics 
2.  Press the Unload button once per second until the front panel indicators display the following: 
Indicator  State, Character, or Message 
Status LED 
Amber, solid 
Single-character display 
2 
LCD 
Maint Mode: Select 
Update Drive FW 
3.  Press and hold the Unload button for two seconds to select Update Drive Firmware from FMR Tape. The front panel 
indicators will display the following: 
Indicator  State, Character, or Message 
Status LED 
Amber, solid 
Single-character display 
c, flashing 
LCD 
Update Drive FW 
Load Drive FMR Tape 
4.  Within 60 seconds, insert the FMR cartridge (or the drive will exit Maintenance Mode). 
When you have inserted the FMR cartridge, the drive begins loading the cartridge, and the front panel indicators display the 
following: 
Indicator  State, Character, or Message 
Status LED 
Amber, solid 
Single-character display 
2, flashing 
LCD 
Update Drive FW 
Tape Loading =====  
After the cartridge is loaded the front panel indicators display the following: 
Indicator  State, Character, or Message 
Status LED 
Amber, flashing at 2 Hz 
Single-character display 
2, flashing 
LCD 
Update Drive FW 
Locating =====  
 followed by: 
Update Drive FW 
Reading =====  
The drive will load the updated firmware from the FMR tape into its erasable programmable read-only memory (EPROM) 
area. 