User's Guide
8 Getting Started
Choosing an Installation Location
Choose an installation location that meets the criteria in Table 1. See Specifications on page 59 for more
information about autoloader specifications.
NOTE:
If you are installing the autoloader in a rack, follow the instructions in the
rackmount kit before continuing to Autoloader SCSI Connections
on page
9.
Table 1 Location Criteria
Requirement Criteria
Standalone requirements Select a location that is flat, sturdy, level, and close to a host
system server. Do not place the autoloader on the floor or other
carpeted surfaces.
CAUTION: Do not place the autoloader on its side or
upside down or stack items that weigh more than 5 KG
(11.02 lbs) on top of the autoloader.
Room temperature 10-35º C (50-95º F)
Power source AC power voltage: 100-127 VAC; 200-240 VAC
Line frequency: 50-60 Hz.
NOTE: Locate the AC outlet near the autoloader. The AC
power cord is the product's main AC disconnect device and
must be easily accessible at all times.
Weight 26 lbs (12 kg)
Air quality Minimal sources of particulate contamination. Avoid areas near
frequently used doors and walkways, stacks of supplies that
collect dust, printers, and smoke-filled rooms.
CAUTION: Excessive dust and debris can damage
tapes and tape drives.
Humidity 20-80% RH
Clearance Back Minimum of 15.4 cm (6 inches)
Front Minimum of 30.8 cm (12 inches)
Sides Minimum of 5.08 cm (2 inches)