User's Manual
Technical Specifications 
DLT2000/DLT2500/DLT2700 Cartridge Tape Subsystem A-13 
The tape drive conforms to a modified Class B environment that includes general 
offices and workspaces with: 
•  Conditioned and marginally-conditioned areas with central or 
remote air-conditioning 
•  Complete temperature and humidity controls 
•  Moderate control tolerances 
•  Systems capable of maintaining comfort levels (for example, typical 
offices and general work areas) 
•  Marginal heating or cooling apparatus 
•  No humidity conditioning 
•  Uncontrolled tolerances 
•  Systems inadequate to maintain constant comfort levels (for 
example, marginal offices and work spaces) 
A.4.1 Temperature and Humidity 
Table A-8 lists the operating temperature and humidity ranges. 
Table A-8 Operating Ranges  
Temperature Range  10 to 40°C 
Temperature Gradient  11°C/h (across the range) 
Temperature Shock  10°C (over two min) 
Relative Humidity  20 to 80% noncondensing 
Humidity Gradient  10%/h 
Table A-9 lists the power-on ranges. 
Table A-9 Power-on Ranges—No Tape Loaded (Unpacked - 72 hours)    
Dry bulb temperature  10 to 40°C 
Temperature gradient  15°C/h (across the range) 
Temperature shock  15°C (over two min) 
Relative humidity  10 to 90% 
Humidity gradient  10%/h 