E. Chimney and Exhaust Connection
1. Chimney & Connector: Use or 4 inch (76-10mm)
diameter type "L" or "PL" venting system. It can be vented
vertically or horizontally.
2. Mobile Home: Approved for all Listed pellet vent. As
with all installations a Quadra-Fire Outside Air Kit must
be used with manufactured home installations.
3. INSTALL VENT AT CLEARANCES SPECIFIED BY THE
VENT MANUFACTURER.
4. Secure exhaust venting system to the appliance with at
least screws 180 degrees apart. Also secure all connec-
tor pipe joints with at least screws through each joint.
NOTE: All pipe must be welded seam pipe whenever
possible. Seal pipe joints with high temperature silicone
(500°F [260°C] minimum rated only).
NOTE: If burning shelled eld corn, you must use
approved venting specically designed for corn. Follow
the instructions from the venting manufacturer.
• Only LISTED venting components may be used.
• NO OTHER vent components may be used.
• Substitute or damaged vent components may impair
safe operation.
WARNING! RISK OF FIRE!
WARNING! RISK OF INJURY OR PROPERTY
DAMAGE!
• Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage.
• Refer to the owner’s information manual provided with this
appliance.
• For assistance or additional information consult a qualied
installer, service agency or your dealer.
The table below can help you calculate the equivalent feet
of pipe which is a method used to determine pellet vent size.
Figure 40.1.
F. Equivalent Feet of Pipe
Figure 40.1
ft.
ft.
ft.
ft.
Example of 3 Elbow-Rear Vent Termination Calculation
Pellet Venting
Component
# of
Elbows
Feet of
Pipe
Multiplied
By
Equivalent
Feet
Components
Equivalent Feet
90
o
Elbow or Tee
X 5 15
45
o
Elbow
X 3
Horizontal Pipe
7 X 1 7
Vertical Pipe
2 X 0.5 1
Total Equivalent Feet 23
Note: This is a generic example and is not
intended to represent any specic fuel type.
Vent surfaces get HOT, can cause burns
if touched. Non-combustible shielding or
guards may be required.
WARNING
CAUTION!
• Do NOTconnectthisunittoachimneyueservicing
another appliance.
• Do NOT connect to any air distribution duct or system.