C. Ceiling Firestop/Floor Penetration Framing
MUST
SLP Pipe
WARNING! Risk of Fire! DO NOT pack insulation around
the vent. Insulation must be kept back from the pipe to
prevent overheating.
D. Install Attic Insulation Shield
WARNING! Fire Risk. DO NOT allow loose materials or
insulation to touch vent. Hearth & Home Technologies
requires the use of an attic shield.
attic insulation shield according to instructions included
Figure 5.3 Installing Ceiling Firestop
Figure 5.4 Installing the Attic Shield
INSTALL ATTIC INSULATION SHIELDS
BEFORE OR AFTER INSTALLATION OF VENT SYSTEM
CEILING FIRESTOP
INSTALLED BELOW CEILING
CEILING FIRESTOP
INSTALLED ABOVE CEILING
ATTIC ABOVE
A
PIPE
SLP
A
9 in. (229 mm)
A