Installation manual

Quadra-Fire • SAPH-MBK-IPI, SAPH-D-PMH-IPI, SAPH-D-MBK-IPI, SAPH-D-CSB-IPI Installation Manual • 2343-980_R8 • 11/1427
10 in. x 10 in. (254mm x 254mm)
framed opening in wall
Studwall
Masonry
Chimney
Retro Connector
(4) Masonry Bolts
(Not Included)
Wall Thimble Cover
Cut and bend flashing as needed
to fit
Sealant adhesive
Figure 4.26
         

      
           


        

          

 
         
bottom and out the opening in the masonry wall, forming


WARNING! Risk of Fire, Explosion or Asphyxiation!
Improper support may allow vent to sag and separate. Use
vent run supports and connect vent sections per installation
instructions. DO NOT allow vent to sag below connection
point to appliance.
7. 




 


 ce the center point of the penetration has been
         
         
          


(254mm) square opening in the wall (centered around
         
           
(254mm) opening is still needed, but does not need to be

This allows the retro connector to mount directly on
       
combustibles
Figure 4.25
 

flashing is larger than the top of the chimney, cut and fold

NOTE: For hearth applications, refer to page 29 for the use of a
co-axial to co-linear appliance connector.