Owner`s manual
Page 10
7050-128B
September 3, 2009
Santa Fe Pellet Stove
R
*L Exception for Horizontal Installations:
USA
INSTALLATIONS: The non-combustible fl oor protector
must be 1/2 inch (13mm) minimum thickness, “k” value = 0.49.
Floor protection requires Type II thermal protection R = 1.0 or
greater.
A
non-combustible fl oor protection extending beneath the
fl u e pipe is recommended
with horizontal venting or under
the top vent adapter with vertical installation. Figure 10.2.
CANADA INSTALLATIONS: A
non-combustible fl o or pro-
tection extending beneath the fl ue pipe is r
equired
with
horizontal venting or under the top vent adapter with vertical
installation.
Must extend 2 inches (51mm) beyond each
side of pipe (shaded area)
C. Hearth Pad Requirements (UL and ULC)
Use
a non-combustible fl oor protector, extending beneath
appliance and to the front, sides and rear as indicated.
Measure front distance “M” from the surface of the glass
door.
Hearth Pad Requirements
Inches
K
Sides 2
L*
Back 2
M
Front 6
L*
K
K
M
Figure 10.2
Figure 10.1
Hearth Pad Requirements
Millimeters
K
Sides 203
L*
Back 51
M
Front 457
USA
Hearth Pad Requirements
Canada Hearth Pad Requirements