Santa Fe Pellet Insert
Mark area of
floor to cut
Starter hole
Keep sharp edge of
metal floor away from
power cord
H.
Removing Metal Floor of Factory-Built Firebox
• The rebrick (refractory), glass doors, screen rails, screen mesh
and log grates can be removed from a factory-built rebox in
order to gain minimum insert opening requirements.
Any smoke shelves, shields and baf es may be removed from
a factory-built rebox if attached with mechanical fasteners.
• The metal oor of the factory-built rebox may be removed to
facilitate the installation of the insert only when a 1/4 (6mm)
inch airspace is provided between the insert and the oor of
outer wrap.
Figure 11.1. Measure and mark the metal oor for cutting. With a
drill, make a starter hole in each corner.
Figure 11.2. Using a saws-all, cut out the oor.
Figure 11.3. Ensure that the power cord can not be damaged by
the sharp metal edge. You may need to cut out a notch to accom-
modate the cord.
The following is only one example as there are many differ-
ent models of factory-built replaces.
NOTE: If the oor is made of thin metal, we recommend using the
2 x 4 from the insert packaging to support the insert. The 2 x 4
may need to be cut to the appropriate size. Ensure that the level-
ing leg is positioned over the 2 x 4 before leveling the insert.
The replace must not be altered, except for the
exceptions listed below. Do not removal the bricks
and mortar from the existing replace.
The following modi cations are premissible:
Removal of damper or locked in open position
Removal of smoke shelf or baf e
Removal of ember catches
Removel of re grate
Removal of view screen/curtain
Removal of doors
• External trim pieces which do not affect the operation
of the replace may be removed providing they can
be stored on or within the replace for reassembly if
the insert is removed.
The permanent metal warning label provided must be
attached to the back of the replace, with screws or
nails, stating that the replace may have been altered
to accommodate the insert, and must be returned to
original condition for use as a conventional replace.
Figure 12.4.
If the hearth extension is lower than the replace
opening, the portion of the insert extending onto the
hearth must be supported.
Manufacturer designed adjustable support kit can be
ordered from your dealer.
Final approval of this installation type is contingent
upon the authority having jurisdiction.
I. Altering the Factory-Built Fireplace
NOTE: Refer to chimney liner manufacturer for
recommendations on supporting the liner. Instal-
lation into replaces without a permit will void the
listing
250-2061
WARNING
THIS FIREPLACE MAY HAVE BEEN ALTERED
TO ACCOMMODATE AN INSERT. IT MUST BE
RETURNED TO ITS ORIGINAL CONDITION
BEFORE USE AS A SOLID FUEL BURNING
FIREPLACE.
250-2061
Figure 11.4