Installation manual

6/27/2014 7019-230A 9
Santa Fe Pellet Insert
A
B
C
D
D. Minimum Opening for Masonry and Zero
Clearance Fireplaces
Inches Millimeters
A
Insert side to combustible side wall 16 406
B
Insert top to mantel 12 305
C
Insert top to maximum. 2-1/4 inch (57mm)
face trim
4-3/4 121
D
Insert side to maximum. 2-1/4 inch (57mm)
face trim
10 254
Location Inches Millimeters
A
Rear Width 24 610
B
Depth 16 406
C
Height 23-1/4 591
D
Front Width 29-1/4 743
Figure 9.1
C. Masonry and Zero Clearance Fireplaces
Inches Millimeters
E
Floor protection hearth extension from door
opening
6 152
F
Floor protection to the side of door opening 6 152
F. Floor Protection
Figure 9.2
Side Wall
Mantel
Maximum Mantel Depth: 12 inches (305mm)
Face
Trim
E
F
A
D
C
B
G. Prefabricated Metal Chimney
The chimney can be new or existing, masonry or prefabricated
and must meet the following minimum requirements:
Must be minimum 6 inch (152mm) inside diameter of
high temperature chimney listed to UL 103 HT (2100
o
F)
or ULC-S629.
Must use components required by the manufacturer for
installation.
Must maintain clearances required by the manufacturer
for installation.
Refer to manufacturers instructions for installation
•The original factory-built clearance replace chimney
cap must be re-installed after installing the approved
chimney liner meeting type UL 103 HT requirements
(2100°F) per UL 1777.
•If the chimney is not listed as meeting HT requirements,
or if the factory built replace was tested prior to 1998, a
full height listed chimney liner must be installed from the
appliance ue collar to the chimney top.
•The liner must be securely attached to the insert ue collar
and the chimney top.
•The air ow of the factory-built zero-clearance replace
system must not be altered. The ue liner top support
attachment must not reduce the air ow for the existing
air-cooled chimney system.
•No dilution air is allowed to enter the chimney.
1. Secure the replace damper in the open position. If
this cannot be accomplished, it will be necessary to
remove the damper
2. Seal damper area of chimney around chimney
connector with a high temperature sealant or seal
insert against the face of the replace.
3. Both methods must be removable and replaceable
for cleaning and re-installation.
NOTE
It is necessary to permanently seal any opening between
the masonry of the replace and the facing masonry.
E. Hearth Extension
If employing a hearth extension, any parts or materials used
in construction must be non-combustible.