Installation manual
8 7019-230A 6/27/2014
Santa Fe Pellet Insert
Fire Risk
Comply with all minimum clearances
to combustibles as specifi ed.
Failure to comply may cause house
fi re.
WARNING
NOTE:
• Illustrations refl ect typical installations and
are FOR DESIGN PURPOSES ONLY.
• Illustrations/diagrams are not drawn to
scale.
• Actual installation may vary due to
individual design preference.
A
C
B
D
C
B
0 in. Clearance To Exposed Section And Face Trim
C
L
B. Clearance To Combustibles, UL and ULC
Inches Millimeters
A Top of Hopper Top Vent 2.0 51
Rear Vent 2.5 64
B Side of Hopper Top or Rear Vent 2.0 51
C Back of Hopper Top or Rear Vent 2.5 64
D Vent Pipe to Combustible Top or Rear Vent 3.0 76
12 in
(305mm)
Combustible
Mantel
6 in
(152mm)
Outside Air
Top Vent:
2 in. (51mm)
Rear Vent:
2.5 in (64mm)
Back of Hopper:
2.5 in (64mm)
Vent Pipe to
Combustibles:
3 in (76mm)
INSTALLED AS A BUILT-IN UNIT
Shown with Rear Vent and Optional Outside Air
Figure 8.1
Figure 8.2
AS A BUILT-IN