Owner`s manual

Quadra-Fire • QFI30-C, QFI35-C • 2227-901 Rev. Q • 3/1518
Figure 5.2 Fireplace Opening
In addition to these dimensions, also reference Clearances and Mantel Projections (Section 5.B).
MINIMUM FIREPLACE SIZE
Location
QFI35-C QFI30-C
Inches Millimeters Inches Millimeters
A Rear Width 23-7/16 595 20-3/16 513
B Front Width 34-5/8 879 30-5/8 778
C Glass Opening Width 31-5/8 803 27-1/2 699
D Glass Opening Height 15-11/16 398 12-3/16 310
E Height-Front 24-1/16 611 20-7/16 519
F Height-Rear 21-1/8 537 17-5/8 448
G** Unit Depth 15-3/4 400 14-3/4 375
H Venting Depth 10-5/8 270 9-1/2 241
I
Height to Top of
Glass Frame
21-5/8 549 18-1/4 464
* Note: If exhaust collar on insert and replace damper do not line up, add 4 inches (102 mm) to minimum
replace height for bends in vent pipe.
**Unit depth is measured to the back of the surround to give the depth needed for installation.
TOP VIEW
FRONT VIEW SIDE VIEW
E
D
C
I
F
B
A
G
H