Installation manual

June 19, 2014 7036-188C 11
MT VERNON AE INSERT
I. Altering the Factory-Built Fireplace
The replace must not be altered, except for the exceptions
listed below. Do not remove the bricks and mortar from
the existing replace.
The following modi cations are permissible:
Removal of damper or locked in open position
Removal of smoke shelf or baf e
Removal of ember catches
Removal of re grate
Removal of view screen/curtain
Removal of doors
• External trim pieces which do not affect the operation of
the replace may be removed providing they can be stored
on or within the replace for reassembly if the insert is
removed.
The permanent metal warning label provided must be
attached to the back of the replace, with screws or
nails, stating that the replace may have been altered to
accommodate the insert, and must be returned to original
condition for use as a conventional replace. Figure 11.1
If the hearth extension is lower than the replace opening,
the portion of the insert extending onto the hearth must be
supported.
Manufacturer designed adjustable support kit can be
ordered from your dealer.
Final approval of this installation type is contingent upon
the authority having jurisdiction.
NOTE: Refer to chimney liner manufacturer for recom-
mendations on supporting the liner. Installation into
replaces without a permit will void the listing
NOTICE: In Canada when using a factory-built chimney it
must be safety listed, Type UL103 HT (2100
o
F) [1149
o
C]
CLASS “A” or conforming to CAN/ULC-S629M, STAN-
DARD FOR 650
o
C FACTORY-BUILT CHIMNEYS.
250-2061
WARNING
THIS FIREPLACE MAY HAVE BEEN ALTERED
TO ACCOMMODATE AN INSERT. IT MUST BE
RETURNED TO ITS ORIGINAL CONDITION
BEFORE USE AS A SOLID FUEL BURNING
FIREPLACE.
250-2061
Figure 11.1
H. Prefabricated Metal Chimney
The chimney can be new or existing, masonry or prefabricated
and must meet the following minimum requirements:
Must be minimum 6 inch (152mm) inside diameter of
high temperature chimney listed to UL 103 HT (2100
o
F)
or ULC-S628.
Must use components required by the manufacturer for
installation.
Must maintain clearances required by the manufacturer
for installation.
Refer to manufacturers instructions for installation
•This insert is listed to ASTM E 1509 Standard and is
approved for installation into listed factory-built zero
clearance replaces listed to UL 127 conforming to the
following speci cations and instructions:
•The original factory-built clearance replace chimney
cap must be re-installed after installing the approved
chimney liner meeting type UL 103 HT requirements
(2100°F) per UL 1777.
•If the chimney is not listed as meeting HT requirements,
or if the factory built replace was tested prior to 1998, a
full height listed chimney liner must be installed from the
appliance ue collar to the chimney top.
•The liner must be securely attached to the insert ue collar
and the chimney top.
•The air ow of the factory-built zero-clearance replace
system must not be altered. The ue liner top support
attachment must not reduce the air ow for the existing
air-cooled chimney system.
•No dilution air is allowed to enter the chimney.
1. Secure the replace damper in the open position. If
this cannot be accomplished, it will be necessary to
remove the damper
2. Seal damper area of chimney around chimney
connector with a high temperature sealant or seal
insert against the face of the replace.
3. Both methods must be removable and replaceable
for cleaning and re-installation.
Fire Risk.
Follow venting manufacturer’s clearances and
instructions when installing venting system.
WARNING