Owner`s manual
R
January 17, 2007
7036-135B
Page 11
Mt. Vernon Pellet Insert (AE)
4
Vent Information
Do not terminate vent in any enclosed or semi-enclosed
area such as a carport, garage, attic, crawl space, under a
sun deck or porch, narrow walkway or closely fenced area,
or any location that can build up a concentration of fumes
such as a stairwell, covered breezeway, etc.
CAUTION
4
Vent Information
A. Venting Termination Requirements
Termination must exhaust above air inlet elevation. It is recom-
mended that at least 60 inches (1524mm) of vertical pipe be
installed when appliance is vented directly through a wall. This
will create a natural draft, which will help prevent the possibility of
smoke or odor venting into the home during a power outage. It will
also keep exhaust from causing a nuisance or hazard by exposing
people or shrubs to high temperatures. The safest and preferred
venting method is to extend the vent vertically through the roof.
J or K
X
V
M
I
H
A
V
G
B
V
V
A
B
V
F
V
C
B
B
E
L
V
D
V
Electrical
Service
V
N
V
N
V
N
N
V
Inside Corner
FIXED
CLOSED
OPEN
OPEN
FIXED
CLOSED
V
X
G
G
Termination Cap
Air Supply Inlet
Gas Meter
Restricted Area
O
P
Figure 11.1
A 12 in. Above Finish Grade (the grade surface
must be a non-combustible material.
B 12 in.
48 in. no OAK
Open door or window: below or to the side
B 12 in. Open door or window: above
C 6 in. Permanently closed window: above, below
or to the side
D 18 in.
36 in. no OAK
Vertical clearance to a ventilated soffi t
located above the terminal within a hori-
zontal distance of 2 ft from the center-line
of the terminal
E 12 in. Clearance to unventilated soffi t
F 12 in. Clearance to outside corner
G 12 in. Clearance to inside corner
H 36 in. Above gas meter/regulator measured from
horizontal center-line of regulator
I 36 in. USA
72 in. Canada
Clearance to service regulator vent outlet
J 12 in.
48 in. no OAK
Clearance to non-mechanical air supply
inlet to the building or the combustions air
inlet to any other appliance
K 10 ft horizontal
3 ft vertical
Clearance to mechanical air supply
L 7 ft. Above paved sidewalk, paved driveway
located on public property
M 12 in. Under an open veranda, porch, deck or
balcony
N See Note 1 Electric service: above, below or to the
side (location must not obstruct or interfere
with access).
O 24 in. Adjacent building, fences and protruding
parts of the structure
P 12 in. Clearance above roof line for vertical
terminations
NOTE; All minimum clearances are listed with an Outside Air Kit (OAK) installed, unless
otherwise noted in table below.
24 in. Above grass, top of plants, wood or any other com-
bustible
12 in.
36 in. no OAK
Clearance from any forced air intake of other appli-
ance
12 in. Clearance horizontally from combustible wall
15 in. Vented directly through a wall, minimum length of
horizontal pipe
6 in. horizontal
12 in. vertical
Minimum horizontal or vertical terminations must
protrude from wall
NOTE 1: Consult local building, fi re offi cials or authorities
having jurisdiction.
NOTE 2: Local codes or regulations may require different clear-
ances.