Installation manual

14 7061-197D November 7, 2014
Explorer II Medium Wood Stove
50.75
29.13
60.25
19.22
42.63
16
(FRONT DOOR OPENING)
36 in.
minimum
8 in.
35 1/4 in.
minimum
16 in. from glass
Fuel door opening
Figure 14.2
Figure 14.1
Figure 14.3
Must extend 2 in.
(51mm) beyond
each side of pipe
(shaded area)
203mm (8 in.)
203mm
(8 in.)
203mm
(8 in.)
457mm (18 in.)
1175mm
(46-1/4 in.)
minimum
1143mm (45 in.)
minimum
A. Hearth Protection Requirements
FLOOR PROTECTION: Floor protector must be non-combus-
tible material, extending beneath heater and to the front, sides
and rear as indicated. The oor must be non-combustible or
otherwise adequately protected from radiant heat given off by
the unit and from sparks and falling embers. A layer of thin
brick or ceramic tile over a combustible oor is not suf cient.
I
t is necessary to install a oor protector of a minimum of 3/8
inch (9.5mm) thick metal clad millboard or equivalent a min-
imum of 16
inches (406mm) in front of glass and 8 inches
(203mm) to both sides of the fuel loading door. Open the
door and measure 8 inches (203mm) from the side edge of
the opening in the face of the appliance. *See exception.
In Canada, similar oor protection must be provided 18 inches
(457mm) in front and 8 inches (203mm) from the sides and
rear of the stove. Figure 14.2
*EXCEPTION: Non-combustible floor protections must
extend beneath the ue pipe when installed with horizontal
venting and extend 2 inches (51mm) beyond each side. See
Figure 14.4
WARNING
Fire Risk.
Hearth pads must be installed exactly as speci ed.
High temperatures or hot embers may ignite concealed
combustibles.
54.25
31.63
63.88
19.22
16
(FRONT DOOR OPENING)
Figure 14.3
USA
CANADA
5 Appliance Set-Up
Corner hearth pad dimensions
with single wall pipe
Corner hearth pad dimensions
with double wall pipe