Owner`s manual

Page 15Quadra-Fire • COLBAY-FS-B • 250-5195 Rev. R • 10/11
NOTE: Maximum number of 45° elbows permitted for a
vertical installation is eight, provided their installation does
not decrease maximum allowable horizontal run (as specified
by vent graph, on page 11).

35 ft. (11m)
MAXIMUM
NOTE: Maximum vertical rise allowable is 35 ft. (11m)
).
2'
1'
2'
1'
1'
NOTE: Maximum number of 90° elbows permitted for a
vertical installation is four, provided the termination falls
within the shaded area shown in vent graph on page 10. See
also , within the four 90° elbows configuration,
the maximum allowable pipe length on the horizontal runs is
1 ft. (305mm) the minimum allowable pipe length on vertical
runs is 1 ft. (305mm).
ADDITIONAL RESTRICTION: This installation may not
have two horizontal sections connected by 90° elbows.


Check the installation instructions for required 1 in. (25mm)
clearances (air space) to combustibles when passing
through ceilings, walls, roofs, enclosures, attic rafters, or
other nearby combustible surfaces. See page 16, 
 Check the instructions below for maximum vertical rise
of the venting system, and any maximum horizontal offset
limitations. All offsets must fall within the set parameters of
the vent graph () located on page 11.



VERTICAL
TERMINATION
CAP
STORM
COLLAR
FLASHING
FIRESTOP
PIPE
LENGTH
SUPPORT
BOX
Fire Risk.
Explosion Risk.
Maintain vent clearance to combustibles as speci-
ed.

Do not pack air space with insulation or other
materials.
Failure to keep insulation or other materials away
from vent pipe may cause fi re.