Owner`s manual
Page12
7014-179D
December 16, 2011
R
CB 1200 Pellet Stove
Improperinstallation,adjustment,alteration,serviceor
maintenancecancauseinjuryorpropertydamage.Refer
totheowner’sinformationmanualprovidedwiththisappli-
ance.Forassistanceoradditionalinformationconsulta
qualiedinstaller,serviceagencyoryourdealer.
WARNING
The chart will help you in determining proper
ventingsizeaccordingtotheequivalentfeetof
pipecalculatedaboveandthealtitudeabovesea
levelofthisinstallation.Figure 12.2.
Locatethecalculatedequivalentfeetofpipeon
theverticalleftsideof thechart. Movetothe
right horizontally on the chart until you reach
youraltitudeabovesealevel.
Ifyoufallbelowthediagonalline,3or4inch(76
to102mm)pipemaybeused.Ifitisanywhere
abovethediagonalline,a4inch(102mm)diam-
eterpipeisrequired.
Thechartrevealsthata90°elbowis5timesas
restrictive to the ow of exhaust gases under
positivepressureas1footofhorizontalpipe,and
afootofhorizontalpipeistwiceasrestrictiveas
afootofverticalpipe.
D. Pipe Selection Chart
Thetablebelowcanhelpyoucalculatetheequivalentfeet
ofpipewhichisamethodusedtodeterminepelletventsize.
Figure 12.1.
C. Equivalent Feet of Pipe
Example of 3 Elbow-Rear Vent Termination Calculaton
Figure 12.1
FireRisk.
DoNOTpackinsulationorother
combustiblesbetweenrestops.
• ALWAYS maintain specied clearances
aroundventingandrestopsystems.
• Installrestopsasspecied.
Failuretokeepinsulationorothermaterial
awayfromventpipemaycausere.
WARNING
3 in. or 4 in. (76mm or 102mm) Diameter Pipe
Equivalent Pipe
Length In Feet
ALTITUDE IN THOUSANDS OF FEET
0
20
30
1 2 3 4 5 6 7 8 9 10
4 in. (102mm) Diameter Pipe Only
10
Example 1
Example 2
Figure 12.2
3 ft
(914mm)
2 ft (609mm)
2 ft (609mm)
2 ft (609mm)
Pellet Venting
Component
# of
Elbows
Feet of
Pipe
Multipled
By
Equivalent
Feet
Components
Equivalent Feet
90
o
ElboworTee
3 X 5 15
45
o
Elbow
X 3
HorizontalPipe
7 X 1 7
VerticalPipe
2 X 0.5 1
TotalEquivalentFeet 23
Note:Thisisagenericexampleandisnot
intendedtorepresentanyspecicfueltype.
Example 1:Iftheequivalentlengthofpipeis23feet
(7m)withaltitudeof8,000feet(2438m)youmustuse
4inch(102mm)diametertype“L”or“PL”vent.
Example 2:Iftheequivalentlengthofpipeis12feet
(3.7m)withaltitudeof6,000feet(1829m) you may
use3or4inch(76to102mm)diametertype“L”or
“PL”vent