Owner`s manual
Page16
7037-135H
December 16, 2011
R
4300 Wood Stove Series (ACC)
NOTE: InCanadawhenusingafactory-builtchimneyitmust
besafetylisted, Type UL103 HT (2100
o
F) CLASS “A” or
conformingtoCAN/ULC-S629M, STANDARD FOR 650
o
C
FACTORY-BUILT CHIMNEYS.
5
Chimney Requirements
Floor
Protector
Chimney
Connector
Insulated"T"
Flashing
Listed Termination Cap
Trim Collar on
InsideWall
ListedChimney
StormCollar
Wall Support
RoofBrace(ifrequired)
Thimble
Floor
Protector
Chimney
Connector
CeilingSupport
ListedChimney
Listed TerminationCap
StormCollar
Flashing
Figure 16.1 Prefabricated Exterior Chimney
Figure 16.2 - Prefabricated Interior Chimney
A. Venting Components
Chimney Connector:
Itis alsoknownasuepipeorstovepipe.Thechimney
connectorjoinsthestovetothechimney.Itmustbea6inch
(152mm)minimumdiameter24gaugemildsteelblackor
26gaugebluedsteel,oranapprovedair-insulateddouble
wallventingpipe.
Thimble:
A manufactured or site-constructed device installed in
combustible walls through which the chimney connector
passes to the chimney. It is intended to keep the walls
from igniting. Site constructed thimbles must meet
NFPA 211 Standards. Prefabricated must be suitable
for use with selected chimney and meet UL103Type HT
Standards.Followinstructionsprovidedbythemanufacturer
for manufactured thimbles for masonry chimney and
prefabricatedchimneys.
Chimney:
Thechimneycanbeneworexisting,masonryorprefabricated
andmustmeetthefollowingminimumrequirementsspecied
inSection5B.
B. Chimney Systems
• Must be minimum 6 inch (152mm) diameter (ID) high
temperaturechimney listed toUL103HT(2100
o
F)or
ULCS629M.
• Mustusecomponentsrequiredbythemanufacturerfor
installation.
• Mustmaintainclearancesrequiredbythemanufacturer
forinstallation.
• Refertomanufacturersinstructionsforinstallation.
Prefabricated Metal Chimney