Owner`s manual
Page12
7037-135H
December 16, 2011
R
4300 Wood Stove Series (ACC)
A. Hearth Protection Requirements
FLOOR PROTECTION: Floorprotectormustbenon-com-
bustiblematerial,extendingbeneathheaterandtothefront,
sidesand rear as indicated. The oor must be non-com-
bustibleorotherwiseadequatelyprotectedfromradiantheat
givenoffbytheunitandfromsparksandfallingembers.A
layerofthinbrickorceramictileoveracombustibleooris
notsufcient.
For US installations,i
tisnecessarytoinstallaoorprotector
ofaminimumof3/8inch(9.5mm)thickmetalcladmillboard
orequivalenta minimum of16
inches(406mm)in front of
glassand8inches(203mm)tobothsidesofthefuelloading
door.Openthedoorandmeasure8inches(203mm)from
theside edge of the opening in the faceoftheappliance.
*See exception.
16" from glass
8 in.
Fuel loading door
31-5/8 in.
minimum
41-3/8 in.
minimum
31-5/8in.
27-3/8in.
37in.
40-15/16in.
3-1/16in.
135°
optional
coverage
51-1/16in.
Mustextend2in.(51mm)beyond
eachsideofpipe(shadedarea)
203mm (8 in.)
203mm
(8 in.)
203mm
(8 in.)
457mm (18 in.)
1334mm
(52-1/2 in.)
minimum
1066mm (42 in.)
minimum
In Canada, similar oor protection must be provided 18
inches (457mm) in frontand 8 inches (203mm) from the
sidesandrearofthestove.*See exception.
*EXCEPTION: Non-combustible oor protections must
extendbeneaththeuepipewheninstalledwithhorizontal
venting and extend 2 inches (51mm) beyond each side.
See Figure 12.4.
USA required
Canada recommended
Figure 12.3
4
Installation
Figure 12.1
Figure 12.2
Figure 12.4
WARNING
Fire Risk.
• Hearth pads must be installed exactly as
specified.
High temperatures or hot embers may ignite
concealed combustibles.
Millennium Model
USA
USA
CANADA