Operating instructions
4300 ACT Wood Stove Series
Page 8 250-7061C December 10, 2004
R
FLOOR  PROTECTION:    Floor  protector  must  be  noncombustible  material,  extending  beneath  heater  and  to  the 
front/sides/rear  as  indicated.    The  floor  must  be  non-combustible  or  otherwise  adequately  protected  from  radiant  heat 
given off by the unit and from sparks and falling embers. A layer of thin brick or ceramic tile over a combustible floor is not 
sufficient. A listed hearth pad that has a “k” value of .84 or lower meets this requirement.
In USA installations, it is necessary to install a floor protector of 1/2" thick metal clad millboard (“k” value = .84) or equivalent 
at least 16" in front of glass door and 8" to both sides of the fuel loading door. Open the door and measure 8” from the side 
edge of the opening in the face of the stove. See *exception below. 
See Alternate Materials Worksheet on 
Page 9 to determine if alternate floor protection materials are acceptable.
In  Canada,  similar  floor  protection  must  be  provided  18"  (457mm)  in  front  and  8"  (203mm)  from  the  sides  and  rear 
of the stove. See *exception below.
*EXCEPTION:  Non-combustile floor protection must extend beneath the flue pipe when installed with horizontal venting 
and extend 2” (51mm) beyond each side. 
FLOOR PROTECTION
USA 4300 Millennium USA 4300 Step Top Uni-Body
16" from glass
8"
USA
Fuel loading door
4-3/4"
3-1/4"
31-5/8" minimum
40-3/4"
minimum
16" from glass
8"
USA
Fuel loading door
5-1/4"
2-3/4"
31-5/8" minimum
40-1/2"
minimum
CANADA
203mm (8")
203mm
(8")
203mm
(8")
457mm (18")
Millennium
1287mm 
(50-3/4")
minimu
m
1080mm (42-1/2
)
minimum
Millennium 
1054mm (41-1/2")
minimum
Step Top Uni-body
Step Top
1288mm 
(50-1/2")
minimu
m
optional coverage
optional
coverage
26.0"
optional
coverage
USA
40-3/4"
required coverage
16"
31-5/8"
56-5/8"
56-5/8"
30.0"
30.0"
USA -4300 Millinneum
USA 4300 Uni-Body Step Top
optional coverage
optional
coverage
26.0"
optional
coverage
USA
40-1/
2
"
required coverage
16"
31-5/8
"
48-1/2"
48-1/2"
30.0"
30.0"
Canada - Both Models
Horizontal Venting 
Both Models
NOTE: Drawings are for illustration purposes only and are not to scale.
Must extend 2" (51mm) beyond each 
side of pipe (shaded area)
USA - Required
Canada - Recommended