Operating instructions
4300 ACT Wood Stove Series
Page 12 250-7061C December 10, 2004
R
FIGURE 12B
SOLID PACK CHIMNEY WITH METAL SUPPORTS AS A THIMBLE
For the method  of  installation to a  masonry  chimney  shown in Figures  14A &  14B on page  14,  it  will be necessary  to 
purchase a 12” (305mm) long 8" (203mm) inside diameter, section of prefabricated listed solid pack chimney to use as a 
thimble. Purchase a wall spacer, trim collar, and a wall band manufactured to fit the chimney section you purchase.
The safety features of this system are twofold:  1) A 2" (51 mm) air space between the chimney section and combustible 
wall;  and,  2)  The  1"  (25mm)  air  space  around  the  chimney  connector  as  it  passes  through  the  chimney  section  to 
the chimney.
The  location  of  the  opening  through  the  wall  to  the  chimney  must  leave  a  minimum  18"  (457mm)  vertical  clearance 
between  the  connector  pipe  and  the  ceiling  (or  minimum  recommended  from  pipe  manufacturer)  to  prevent  the 
ceiling from catching fire.
Measure for the center-line as shown in Figure 12A below.  Cut an opening in the wall large enough to accommodate the 
outside dimension of the chimney section plus the minimum air space specified by its manufacturer.  It may be necessary 
to cut the wall studs and install a header and a sill frame to maintain the wall support. The hole in the chimney must have 
at least an 8" (203mm) diameter fire clay liner or equivalent, secured with refractory mortar.  If it is necessary to cut a hole 
in the chimney liner, use extreme care to keep it from shattering.
FLOOR 
PROTECTOR
THIMBLE,
12" (305mm) 
OF BRICK
CEILING 
JOIST
COMBUSTIBLE 
WALL
1" (25mm) 
CLEARANCE
AIRTIGHT 
CLEANOUT DOOR
FIRECLAY 
FLUE 
LINER WITH AIR 
SPACE
SHEATHING
EAVE
1" (25mm) CLEARANCE 
WITH FIRESTOP
RAFTER
FLASHING
CONCRETE CAP
WARNING! ALWAYS FOLLOW CHIMNEY CONNECTOR MANUFACTURER’S INSTRUCTIONS FOR PROPER INSTALLATION.
CHIMNEY CONNECTOR IS TO BE USED ONLY WITHIN THE ROOM, BETWEEN THE STOVE AND CEILING OR WALL, NEVER 
PASSING THROUGH A COMBUSTIBLE CEILING OR WALL.  THE CONNECTOR SHALL NOT PASS THROUGH AN ATTIC OR 
ROOF SPACE, CLOSET OR SIMILAR CONCEALED SPACE, OR A FLOOR, OR CEILING.  MAINTAIN MINIMUM CLEARANCES 
TO COMBUSTIBLES AS REFERENCED ON PAGE 7.
Center of Hole
Wa
ll
Center Line
Opening
Center Line
Add  center-line  measurement  to  depth 
measurement of your floor protector.  Mark 
this combined measurement at correct wall 
location  for  your  installation,  maintaining 
minimum clearance to combustibles, and 
mark wall for a 10" x 10" (254mm x 254mm) 
square hole. 
FIGURE 12A










