Owner's Manual

10
TD-001572-01-A
Remote
Remote provides the capability of controlling and monitoring the
status of the amplifier from a remote location. Figure 11
One per amplifier
3.5 mm Euro, 5-pin (black)
Standby
The REMOTE STBY contacts provide the functionality to put the
amplifier into standby, and to take it out of standby from a remote
location. Figure 12
Connect the two STBY pins on the REMOTE connector to the
two pins of a toggle switch.
When the switch is open, the amplifier is not in standby.
NOTE: If the amplifier is in standby because of a no-signal time-out, in protect mode, or
off, closing and opening the switch has no effect on the amplifier status.
When the switch is closed, the amplifier goes into standby.
Relay
The REMOTE RELAY provides a means to monitor the amplifier's operating condition with
external equipment. Figure 13
NO = Relay "normally open" terminal
C = Relay "common" terminal
NC = Relay "normally closed" terminal
Amplifier Fault/Standby/Off = Relay NOT Energized, C & NC terminals connected
Amplifier OK = Relay Energized, C & NO terminals connected
IMPORTANT!: Nominal switching capacity is 30 VDC at 1 A for a total of
30 W maximum. The maximum voltage is 220 VDC if the current is limited to
observe the maximum power rating (30 W).
— Figure 11 —
NO
NC
C
Not
Standby
Standby
— Figure 12 —
Switch
closed:
Standby
Switch
open: Not
Standby
Amplifier is OFF, relay
is not energized
Amplifier is ON, relay
is energized
— Figure 13 —
C
NO NC
C
NO NC