Instruction Manual

*Available with 2 elements
Clearance Chart:
For safe and efficient operation, maintain at least the following
minimum clearances at all times (See Fig. 1):
Bottom of Heater to Finished Floor:
Front Inlet Models: (max 250 watts per foot)
- May be installed on floor if under 250 watts per foot.
However, for best performance, install bottom of heater
approximately 3 inches (76 mm) off floor. For models 250
watts per foot or more, bottom of units must be mounted at
least 2” off floor.
Bottom Inlet Models:
- 100-250 watts per foot 2 inch (51 mm)
Top of Heater to Ceiling (all models):
- Minimum 36 inches (914 mm)
Top of Heater to Bottom of Drapes (See Example 2):
- Minimum 6 inches (152 mm)
IMPORTANT NOTE:
Certain fabrics and vinyl materials (such
as vinyl blinds) may become damaged by the heated air from
the heater and should not be installed above the heater.
Front of Heater to Full Length Drapes (See Example 1):
- Minimum between bottom of drapes and floor 2-1/2 inches
(64 mm)
- Minimum between top of drapes and ceiling 1/2 inch (13
mm)
- Minimum between front of heater and nearest fold of drape
2 inches (51 mm)
Top of Heater to Bottom of Window Sill:
- Minimum 12 inches (305 mm)
2
No. 12 AWG
No. 10 AWG
No. 8 AWG
5
4
2
7 Amps
9 Amps
12.0 Amps
5 Amps
7 Amps
10 Amps
4.5 Amps
6 Amps
-
Copper wire
size 90º C
Max. No.
wire installed
in wireway
Up to 2
conductors
3 to 4
conductors
4 to 5
conductors
Maximum Allowable Current
Table B. Sizing Field Installed Wiring
Catalog Length Watts Total
Amperage
Number "L" per ft. Watts 120V 208V 240V 277V 347V 600V
1125 125 250 -- -- -- -- -- --
1150
24”
150 300 -- 1.4 1.3 -- -- --
1
188 (610mm) 188 376 3.1 1.8 1.6 1.4 -- --
1250 250 500 -- 2.4 2.1 1.8 -- --
2
100 100 200 1.7 1 0.8 -- -- --
2125
28"
125 250 2.1 1.2 1 0.9 -- --
2150 (711mm) 150 300 2.5 1.4 1.3 1.1 -- --
2188 188 376 3.1 1.8 1.6 1.4 -- --
2
250 250 500 4.2 2.4 2.1 1.8 1.4 --
3100 100 300 2.5 1.4 1.3 1.1 -- --
3125
3'
125 375 3.1 1.8 1.6 1.4 1.1 --
3150 (914mm) 150 450 3.8 2.2 1.9 1.6 1.3 --
3188 188 564 4.7 2.7 2.4 2 1.6 --
3250 250 750 6.3 3.6 3.1 2.7 2.2 --
4
100 100 400 3.3 1.9 1.7 1.4 1.2 --
4125
4'
125 500 4.2 2.4 2.1 1.8 1.4 --
4
150 (1219mm) 150 600 5 2.9 2.5 2.2 1.7 --
4188 188 752 6.3 3.6 3.1 2.7 2.2 1.3
4250 250 1000 8.3 4.8 4.2 3.6 2.9 1.7
5100 100 500 4.2 2.4 2.1 1.8 1.4 --
5
125
5'
1
25 625 5.2 3 2.6 2.3 1.8 1
5150 (1524mm) 150 750 6.3 3.6 3.1 2.7 2.2 1.3
5188 188 940 7.8 4.5 3.9 3.4 2.7 1.6
5250 250 1250 10.4 6 5.2 4.5 3.6 2.1
6
100 100 600 5 2.9 2.5 2.2 1.7 1
6125
6'
125 750 6.3 3.6 3.1 2.7 2.2 1.3
6150 (1829mm) 150 900 7.5 4.3 3.8 3.2 2.6 1.5
6188 188 1128 9.4 5.4 4.7 4.1 3.3 1.9
6250 250 1500 12.5 7.2 6.3 5.4 4.3 2.5
7100 100 700 5.8* 3.4 2.9 2.5 2 1.2
7
125
7'
1
25 875 7.3* 4.2 3.6 3.2 2.5 1.5
7
150 (2134mm) 150 1050 8.7 5 4.4 3.8 3 1.8
7188 188 1316 10.9* 6.3 5.5 4.8 3.8 2.2
7250 250 1750 14.5* 8.4 7.3 6.3 5 2.9
8100 100 800 6.7* 3.8 3.3 2.9 2.3 1.3
8125
8'
125 1000 8.3* 4.8 4.2 3.6 2.9 1.7
8150 (2438mm) 150 1200 10 5.8 5 4.3 3.5 2
8188 188 1504 12.5* 7.2 6.3 5.4 4.3 2.5
8250 250 2000 16.7* 9.6 8.3 7.2 5.8 3.3
9100 100 900 7.5* 4.3 3.8 3.2 2.6 1.5
9125
9'
125 1125 9.4* 5.4 4.7 4.1 3.2 1.9
9150 (2743mm) 150 1350 11.2* 6.5 5.6 4.9 3.9 2.3
9188 188 1692 14.1* 8.1 7.1 6.1 4.9 2.8
9250 250 2250 18.8* 10.8 9.4 8.1 6.5 3.8
10100 100 1000 8.3* 4.8 4.2 3.6 2.9 1.7
10125
10'
125 1250 10.4* 6 5.2 4.5 3.6 2.1
10150 (3048mm) 150 1500 12.5* 7.2 6.3 5.4 4.3 2.5
10188 188 1880 15.7* 9 7.8 6.8 5.4 3.1
10250 250 2500 -- 12 10.4 9 7.2 4.2
Table A - DBSL Technical Data
CEILING
FLOOR FLOOR
DRAPES
HEATER
WALL
WALL
CEILING
MIN. 1/2”
(13 mm)
MIN. 2”
(51 mm)
MIN. 2-1/2”
(64 mm)
MIN. 1/2”
(13 mm)
MIN. 6”
(152 mm)
HEATER
DRAPES
Fig. 1: Clearance for Drapery
Example 1
Example 2